The compression ratio is too large
Detect the suction and exhaust pressures and reduce the pressure ratio.
2. The cooling effect of the water-cooled oil cooler has declined
Clean the oil cooler by lowering the water temperature or increasing the water volume.
3. Insufficient liquid supply to the liquid ammonia oil cooler
Analyze the cause and increase the supply of liquid.
4. Inhaling severely overheated steam
Increase the liquid supply volume, enhance the insulation of the suction pipeline, and check whether the bypass valve is leaking.
5. Insufficient fuel injection
Check and analyze the cause, and increase the fuel injection volume.
6. Air seeps into the system
It should be discharged and the cause of air infiltration should be checked for maintenance.